Ratings IP20/UL Open
type/ NEMA 1 option
Type designation Frame
size
IP20
Frame
size
IP66
PN
(kW)
PN
(hp)
I2N
(A)
1-phase AC supply, 200 to 240 V +B063
0.37 0.5 2.4 ACS355-01X-02A4-2 R0-
0.75 1.0 4.7 ACS355-01X-04A7-2 R1-
1.1 1.5 6.7 ACS355-01X-06A7-2 R1-
1.5 2.0 7.5 ACS355-01X-07A5-2 R2-
2.2 3.0 9.8 ACS355-01X-09A8-2 R2-
3-phase AC supply, 200 to 240 V +B063
0.37 0.5 2.4 ACS355-03X-02A4-2 R0 R1
0.55 0.75 3.5 ACS355-03X-03A5-2 R0 R1
0.75 1.0 4.7 ACS355-03X-04A7-2 R1 R1
1.1 1.5 6.7 ACS355-03X-06A7-2 R1 R1
1.5 2.0 7.5 ACS355-03X-07A5-2 R1 R1
2.2 3.0 9.8 ACS355-03X-09A8-2 R2 R3
3.0 3.0 13.3 ACS355-03X-13A3-2 R2 R3
4.0 5.0 17.6 ACS355-03X-17A6-2 R2 R3
5.5 7.5 24.4 ACS355-03X-24A4-2 R3-
7.5 10.0 31.0 ACS355-03X-31A0-2 R4-
11.0 15.0 46.2 ACS355-03X-46A2-2 R4-
3-phase AC supply, 380 to 480 V +B063
0.37 0.5 1.2 ACS355-03X-01A2-4 R0 R1
0.55 0.75 1.9 ACS355-03X-01A9-4 R0 R1
0.75 1.0 2.4 ACS355-03X-02A4-4 R1 R1
1.1 1.5 3.3 ACS355-03X-03A3-4 R1 R1
1.5 2.0 4.1 ACS355-03X-04A1-4 R1 R1
2.2 3.0 5.6 ACS355-03X-05A6-4 R1 R1
3.0 3.0 7.3 ACS355-03X-07A3-4 R1 R1
4.0 5.0 8.8 ACS355-03X-08A8-4 R1 R1
5.5 7.5 12.5 ACS355-03X-12A5-4 R3 R3
7.5 10.0 15.6 ACS355-03X-15A6-4 R3 R3
11.0 15.0 23.1 ACS355-03X-23A1-4 R3-
15.0 20.0 31.0 ACS355-03X-31A0-4 R4-
18.5 25.0 38.0 ACS355-03X-38A0-4 R4-
22.0 30.0 44.0 ACS355-03X-44A0-4 R4-
X within the type designation stands for E or U.
PN for kW = Typical motor power in 400 V at normal use
PN for hp = Typical motor power in 460 V at normal use
I2N for A = Continuous rms current. 50% overload is allowed for
one minute in ten minutes.
Type designation
This is the unique reference number (shown in
column 4, right) that clearly identifies your drive
by current rating and frame size. Once the drive’s
type designation has been selected, the frame
size (column 5) can be used to determine the
drive dimensions, shown on page 12.
Voltages
ACS355 is available in two voltage ranges:
2 = 200 to 240 V
4 = 380 to 480 V
Insert either “2” or “4”, depending on your chosen
construction, current rating, voltage, and option
and variant codes into the type designation.
Current rating
Current rating represents the rated continuous
drive output current inside the drive
specification. Motor power stated in the table
below states the typical motor power.
Variant code
This code states the factory installed SW variants
to the drive. See pages 16 - 19 for details.
Construction
“01E” within the type designation varies
depending on the drive phase and EMC filtering.
Choose below the one you need.
01 = 1-phase
03 = 3-phase
E = EMC filter connected, 50 Hz frequency
U = EMC filter disconnected, 60 Hz frequency
(In case the fi lter is required it can easily
be connected
Cooling and fuses
Cooling
ACS355 is fitted with cooling fans as standard. The cooling
air must be free from corrosive substances and must not be
above the maximum ambient temperature of 40 °C (50 °C
with derating). Heat dissipation from IP66/IP67/UL Type 4X
drive equals to the IP20 UL Open values. For more specific
limits see the Technical specification – Environmental limits
in this catalog.
Cooling air flow
Type designation Frame
size
Heat dissipation Air flow
(W) BTU/hr1) m
3/h ft3/min
1-phase AC supply, 200 to 240 V
2)
ACS355-01X-02A4-2 R0 48 163 –
3-phase AC supply, 200 to 240 V
2)
–
ACS355-01X-04A7-2 R1 72 247 24 14
ACS355-01X-06A7-2 R1 97 333 24 14
ACS355-01X-07A5-2 R2 101 343 21 12
ACS355-01X-09A8-2 R2 124 422 21 12
2)
ACS355-03X-02A4-2 R0 42 142 –
2)
ACS355-03X-03A5-2 R0 54 183 –
3-phase AC supply, 380 to 480 V
2)
–
2)
–
ACS355-03X-04A7-2 R1 64 220 24 14
ACS355-03X-06A7-2 R1 86 295 24 14
ACS355-03X-07A5-2 R1 88 302 21 12
ACS355-03X-09A8-2 R2 111 377 21 12
ACS355-03X-13A3-2 R2 140 476 52 31
ACS355-03X-17A6-2 R2 180 613 52 31
ACS355-03X-24A4-2 R3 285 975 71 42
ACS355-03X-31A0-2 R4 328 1119 96 57
ACS355-03X-46A2-2 R4 488 1666 96 57
2)
ACS355-03X-01A2-4 R0 35 121 –
2)
ACS355-03X-01A9-4 R0 40 138 –
X within the type designation stands for E or U.
1) BTU/hr = British Thermal Unit per hour. BTU/hr is
approximately 0.293 Watts.
2) Frame size R0 with free convection cooling.
2)
–
2)
–
ACS355-03X-02A4-4 R1 50 170 13 8
ACS355-03X-03A3-4 R1 60 204 13 8
ACS355-03X-04A1-4 R1 69 235 13 8
ACS355-03X-05A6-4 R1 90 306 19 11
ACS355-03X-07A3-4 R1 107 364 24 14
ACS355-03X-08A8-4 R1 127 433 24 14
ACS355-03X-12A5-4 R3 161 551 52 31
ACS355-03X-15A6-4 R3 204 697 52 31
ACS355-03X-23A1-4 R3 301 1029 71 42
ACS355-03X-31A0-4 R4 408 1393 96 57
ACS355-03X-38A0-4 R4 498 1700 96 57
ACS355-03X-44A0-4 R4 588 2007 96 57
Free space requirements
Enclosure type Space above
(mm)
Space below
(mm)
Space on left/right
(mm)
All frame sizes 75 75 0
IP66/67 enclosure 75 75 20
Fuses
Standard fuses can be used with ABB machinery drives.
For input fuse connections see table below. Also Manual
Motor Protectors can be used to protect the installation.
See user’s manual for details.
Selection table
Type designation Frame
size
IEC fuses UL fuses
(A)
Fuse
type*) (A)
Fuse
type*)
1-phase AC supply, 200 to 240 V
ACS355-01X-02A4-2 R0 10 gG 10 UL class T
ACS355-01X-04A7-2 R1 16 gG 20 UL class T
ACS355-01X-06A7-2 R1 16/20 1) gG 25 UL class T
ACS355-01X-07A5-2 R2 20/25 1) gG 30 UL class T
ACS355-01X-09A8-2 R2 25/35 1) gG 35 UL class T
3-phase AC supply, 200 to 240 V
ACS355-03X-02A4-2 R0 10 gG 10 UL class T
ACS355-03X-03A5-2 R0 10 gG 10 UL class T
ACS355-03X-04A7-2 R1 10 gG 15 UL class T
ACS355-03X-06A7-2 R1 16 gG 15 UL class T
ACS355-03X-07A5-2 R1 16 gG 15 UL class T
ACS355-03X-09A8-2 R2 16 gG 20 UL class T
ACS355-03X-13A3-2 R2 25 gG 30 UL class T
ACS355-03X-17A6-2 R2 25 gG 35 UL class T
ACS355-03X-24A4-2 R3 63 gG 60 UL class T
ACS355-03X-31A0-2 R4 80 gG 80 UL class T
ACS355-03X-46A2-2 R4 100 gG 100 UL class T
3-phase AC supply, 380 to 480 V
ACS355-03X-01A2-4 R0 10 gG 10 UL class T
ACS355-03X-01A9-4 R0 10 gG 10 UL class T
ACS355-03X-02A4-4 R1 10 gG 10 UL class T
ACS355-03X-03A3-4 R1 10 gG 10 UL class T
ACS355-03X-04A1-4 R1 16 gG 15 UL class T
ACS355-03X-05A6-4 R1 16 gG 15 UL class T
ACS355-03X-07A3-4 R1 16 gG 20 UL class T
ACS355-03X-08A8-4 R1 20 gG 25 UL class T
ACS355-03X-12A5-4 R3 25 gG 30 UL class T
ACS355-03X-15A6-4 R3 35 gG 35 UL class T
ACS355-03X-23A1-4 R3 50 gG 50 UL class T
ACS355-03X-31A0-4 R4 80 gG 80 UL class T
ACS355-03X-38A0-4 R4 100 gG 100 UL class T
ACS355-03X-44A0-4 R4 100 gG 100 UL class T
X within the type designation stands for E or U.
*) According to IEC-60269 standard.
1) If 50% overload capacity is needed, use the bigger fuse alternative.